On the tools

Flue gas analyser readings: how to take and read them

Sample at the point the manufacturer specifies, with the analyser zeroed in fresh air and the appliance run to the stated condition, then judge the settled figures against that model's commissioning data. Where the maker gives none, TB 143's key action levels are CO at or below 350 ppm and a combustion ratio at or below 0.0040.

Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed September 2026

The analyser tells the truth about combustion only if the measurement itself is taken properly: at the sampling point the manufacturer specifies, on the right basis, and after the readings have had time to settle. A figure read too early, or at the wrong point, describes the measurement rather than the appliance.

What readings does a flue gas analyser give you?

Four figures matter on a typical domestic job: carbon monoxide (CO), measured in ppm; carbon dioxide (CO₂), measured as a percentage; the combustion ratio, which is CO divided by CO₂; and oxygen, with flue temperature alongside. Most analysers display the ratio directly, and it can also be worked out from the two readings: with CO in ppm and CO₂ as a percentage, the ratio is CO ÷ (10000 × CO₂), which is exactly what our free calculator does. Each figure answers a different question. CO and the ratio speak to how completely the appliance is burning, CO₂ and oxygen to how much air is in the mix, and flue temperature to what the appliance is doing with the heat it makes.

What do good flue gas readings look like?

Settled, inside the manufacturer's published figures for that model, and with a combustion ratio at or below 0.0040. There is no universal band, and a table that offers you one is selling a shortcut. What does exist is a two-layer answer: the generic key action levels Gas Safe Register's Technical Bulletin 143 gives where a manufacturer sets none, and the specific figures each maker publishes for each appliance. The table below shows both, using two current UK boilers as examples.

What each reading tells you, with example figures from published manufacturer data
ReadingWhat it tells youExample figures from a manufacturer's dataWhat it looks like when something is wrong
CO (ppm)How much carbon monoxide the appliance is making, which is the direct product of incomplete combustion.Below 250 ppm at max and min rate (Worcester Bosch, Greenstar 4000 combi GR4700iW C, read 10 minutes after firing). TB 143 where the maker sets none: 350 ppm or less.Above the maker's figure, or climbing while the appliance runs. A low CO can also be a diluted sample rather than a clean burn, which is why it is never read on its own.
CO₂ (%)How much air is in the mix, so how close the appliance is to the fuel-to-air balance it was set up for.9.0 to 9.8% at max rate; 8.2 to 9.0% at min and at least 0.2 below the max reading taken (Worcester Bosch, Greenstar 4000). 9.2 ± 1.0 Vol% at full load, casing closed (Vaillant, ecoTEC plus VU/VUW ..6/5-5).Outside the maker's window, or a minimum-rate figure that has not stepped down from the maximum-rate one.
O₂ (%)The same air question from the other side, and the reading that exposes a diluted sample.4.5 ± 1.8 Vol% at full load, casing closed (Vaillant, ecoTEC plus VU/VUW ..6/5-5). 20.6% or more with CO₂ below 0.2% at the air inlet test point, which is the flue integrity check (both makers).Oxygen well above the maker's figure at the flue sampling point means air is reaching the sample or the appliance, so the raw CO reading cannot be taken at face value.
Combustion ratio (CO ÷ CO₂)How completely the appliance is burning, screened in a way dilution cannot flatter.0.0040 or less (TB 143 key action level). 0.0031 (Vaillant set values, ecoTEC plus VU/VUW ..6/5-5), so a maker's own figure can be tighter.Above the action level, or above the maker's own figure. Both manuals then send you the same way: the remedial checks in the flowchart, then the manufacturer's technical helpline.
Flue gas temperatureWhat the appliance is doing with the heat it makes, and context for the other four.No generic band. 40 °C minimum, 70 °C maximum (Vaillant technical data, ecoTEC plus VU 126/5-5 to VU 306/5-5).A long way from the model's data at the conditions you are actually running. On its own it is neither a pass nor a fail; treat it as a prompt to confirm the appliance is in the state the test asks for, and read it with the other four.

Read that third column as an example, not a standard. Every figure in it is the maker's natural gas value, and both manuals give different ones for LPG. TB 143 is explicit that the boiler manufacturer's guidance must be followed where it is available, and that makers may set their own, tighter action levels; both appliances above do. Flue gas temperature is the one reading with no commissioning band at all, and Worcester quotes the Greenstar 4000's separately for 80/60 °C and 40/30 °C operation, so what to expect there depends on the flow and return temperatures the appliance is running at. The figures for the boiler in front of you live in its installation instructions, and that book beats anything carried over from the last job.

What do the readings mean when they go wrong?

Read the figures together rather than one at a time, because each pattern points somewhere different. The table below sticks to the causes and actions TB 143 and the two manufacturers' instructions actually name.

Reading patterns, what they point at and what to check
Pattern on the analyserWhat it points atWhat to check
Combustion ratio above 0.0040, or above the maker's tighter figureIncomplete combustion, at a level the manufacturers treat as a stop rather than a note.Work the flowchart in that appliance's instructions. It has you check the seals around the burner, the internal flue seals and the door and case seals, and rectify where necessary; if that does not bring the readings inside the limits, the appliance is turned off and the manufacturer's technical helpline is called. TB 143 is clear that no adjustment of the air/gas ratio valve should be attempted before that call.
CO climbing while CO₂ holds steadyCombustion deteriorating as the appliance runs, which is the pattern the ratio exists to catch.Keep watching rather than recording the first settled-looking number, and take the readings at both maximum and minimum rate. The commissioning process is a check at each rate, with both sets recorded.
O₂ high and CO₂ low togetherAir in the sample: dilution rather than a clean burn, so the raw CO figure is flattering the appliance.Probe position and seal at the test point first, with the cone adjusted so it seals the point and the probe reaches the centre of the flue gas stream. Then flue integrity, which at the air inlet test point means oxygen of 20.6% or more with CO₂ below 0.2%.
At the air inlet test point, O₂ below 20.6% or CO₂ above 0.2%Combustion products and inlet air are mixing, so the flue system needs investigating before anything else is believed.Whether the flue components are assembled, fixed and supported as the boiler and flue manufacturer's instructions require, and whether the flue or terminal is obstructed. The flowchart is blunt here: the appliance must not be commissioned until the problem is identified and resolved.
Figures that never settleThe appliance is not yet in the condition the test asks for, or the sample is not sealed.Give it the time the manual asks for. Worcester's Greenstar 4000 figures are read 10 minutes after firing; Vaillant's are read after at least five minutes at full load. Check the probe seal, and check the appliance can hold the rate: at maximum in test mode a combi may need enough water run through the hot water circuit to stop it cycling on low heating demand.
CO₂ higher than the maker's figureThe mix is rich for the air available, and the appliance is outside the window it was set up for.Worcester's list for a CO₂ out of tolerance: the gas inlet pressure, the gas rate, the fan test pressure, the flue and air intake, and any blockage in the condensate disposal. The air/gas ratio valve is factory set and stays that way unless the manufacturer's helpline says otherwise.

What does a full reading set look like?

Here is a commissioning visit on a Greenstar 4000 combi, walked through against Worcester's published figures. The readings are invented for the example; the figures they are judged against are the manufacturer's.

Worked example: an illustrative reading set judged against the Greenstar 4000's published figures
Stage of the checkWhat the analyser showedThe manufacturer's figureVerdict
Air inlet point, maximum rateO₂ 20.8%, CO₂ 0.1%Oxygen of 20.6% or more, CO₂ below 0.2%Flue integrity confirmed with the combustion casing on, so what comes off the flue sampling point can be trusted to be flue gas.
Flue sampling point, maximum rate, 10 minutes after firingCO 46 ppm, CO₂ 9.2%, ratio 0.0005CO₂ between 9.0 and 9.8%, CO below 250 ppm, ratio at or below 0.0040Inside the window on all three, and the arithmetic checks: 46 ÷ (10000 × 9.2) is 0.0005.
Flue sampling point, minimum rateCO 26 ppm, CO₂ 8.7%, ratio 0.0003CO₂ between 8.2 and 9.0% and at least 0.2 lower than the maximum reading taken, CO below 250 ppm8.7% sits 0.5 below the 9.2% recorded at maximum rate, so the step down the manual asks for is there.
RecordingAll six figures written down at the applianceCO and combustion ratio at maximum and minimum rate, on the commissioning documentationThis is the point of the exercise. HHIC boiler manufacturers treat a completed Benchmark checklist as a condition of warranty, and Gas Safe Register will defect an installation where CO and combustion ratio are not correctly recorded.

Change one number and the visit changes. Had the minimum-rate CO₂ come back at 9.1%, it would be outside Worcester's 8.2 to 9.0% band and only 0.1 below the maximum-rate reading, failing both halves of the same requirement, and the boiler would not be signed off on it. A comfortable ratio does not rescue that, because the ratio is a screening figure and the maker's CO₂ window is a separate condition to satisfy.

What should you check before the probe goes in?

Analyser: right type, in calibration, in competent hands

The Greenstar 4000 instructions ask for an analyser of the correct type as specified in BS 7967, calibrated as its own manufacturer specifies, used by someone competent in it. Know the calibration date before you leave the van, because an expired certificate makes every figure that follows unusable.

Gas type, inlet pressure and gas rate first

The CO and combustion checks come once the gas rate and pressure have been confirmed acceptable, and once the appliance is confirmed as connected to the correct gas type. Combustion figures from an appliance running on the wrong gas rate describe the gas rate, not the burner.

Look at the flue before you measure it

A visual check of the whole flue system, confirming the components are correctly assembled, fixed and supported. Both manufacturers put this ahead of the analyser work, and on an appliance with no air inlet test point it is the only flue integrity check available.

Zero in fresh air

Check and zero the analyser in fresh air as its manufacturer specifies, before it meets any combustion products. Keep the probe out of the flue while the appliance is coming up to condition too: the flowchart warns that inserting it during that period risks flooding the sensor.

Run the appliance to the stated condition

Maximum rate first, set the way that appliance's instructions describe. Worcester's Greenstar 4000 figures are read 10 minutes after firing, Vaillant's after at least five minutes at full load, and neither clock starts until the appliance is actually running at the rate the test asks for.

Sample at the maker's test point, sealed

The probe goes into the flue gas sampling point with the cone adjusted so it seals the point and positions the probe end in the centre of the flue gas stream. The combustion casing stays on while the readings are taken.

Let it settle, then record at both rates

Wait for stable figures and record CO, CO₂ and the ratio, then set the appliance to minimum rate where the instructions specify and do it again. On a new boiler both sets belong on the Benchmark checklist before you leave.

Cap the test points and purge

Refit the test point plugs, make sure the case goes back on correctly, and let the analyser purge clear in fresh air before it returns to its bag, for the sensors' sake and for the next job's readings.

Where the probe goes: concentric flue turret, cross sectionon up to the terminalflue gas outair inboiler, combustion case onconeFlue gas sampling pointCO, CO₂ and the ratioat maximum rate, then minimumafter the maker's settling timeprobe tip in the centrecone sealing the pointAir inlet sampling pointflue integrity checkO₂ 20.6% or moreCO₂ 0.2% or lesscase on, at maximum rateblanking plugs, refit after the testSchematic, not to scale. Sample where the manufacturer's instructions specify.
Where the probe goes, and which check each point is for. The arrangement and the wording follow Worcester Bosch's Greenstar 4000 instructions and the commissioning flowchart in Gas Safe Register's TB 143, both listed under Sources.

What is a dry flue gas reading?

Burning gas produces water vapour as well as carbon dioxide, so the gas in a working flue is wet: part of the sample, by volume, is steam. An electronic analyser does not read it that way. The sample is conditioned on its way to the sensors, with the water vapour condensed out and removed, so the figures on the screen describe the dry products of combustion. That is what “dry flue gas” means, and it is the basis manufacturers use for their commissioning data, which is what makes the comparison valid: a dry reading judged against dry reference figures is like against like. It also means a reading is not something you can sanity-check by eye against the plume at a flue terminal, because the visible cloud is mostly that condensed water, doing something the sensors never saw.

How do you sample a chimney or an open flue?

By the procedure in that appliance's instructions, at the sampling point the manufacturer provides. Where an appliance has no flue gas sampling point and the correct procedure is not specified in its manual, the manufacturers' own commissioning flowchart says to consult them for guidance rather than improvise a position, and on older open-flued kit that is often the honest answer.

The standard behind analyser use here is BS 7967:2015, which covers flueless (type A), open-flued (type B) and room-sealed (type C) appliances, along with any appliance for which the manufacturer has provided a purpose-designed sampling point or specific sampling instructions. It assumes an operative with the relevant ACS competence and equipment conforming to BS EN 50379-3 or BS 7927, and TB 143 points to it for further guidance on using an analyser. TB 143 itself does not stretch this far, and says so on its first page: its subject is commissioning a condensing boiler incorporating air/gas ratio control valve technology, and it explicitly does not apply to service and maintenance work involving that valve.

Probe position matters more in an open flue than anywhere else, because the flue is doing its job by drawing room air. Where a manufacturer gives a test point the instruction is specific: adjust the cone so it seals the point and puts the end of the probe in the centre of the flue gas stream. A probe sitting off-centre, or a point left unsealed, samples a blend of combustion products and room air. That blend lowers CO and CO₂ together, which is what makes a raw CO figure from an open flue such a poor witness, and why the ratio between them is the reading to lean on: dilution moves both of its ingredients at once, so the ratio holds. Oxygen is the tell. Well above what the appliance's data expects and the sample is diluted, whatever the CO figure says.

One check you have on a room-sealed appliance is missing here. The flue integrity check the manufacturers describe, oxygen of 20.6% or more with CO₂ below 0.2%, is taken at an air inlet test point, and an open flue has none. The flowchart covers that case directly: where no air inlet test point is provided, the analyser check is not possible and flue integrity is verified visually instead, before the combustion readings are taken. The spillage test sits alongside all of this rather than inside it. It belongs to the chimney side of the job, under BS 5440-1 and the appliance manufacturer's instructions, and it asks a different question: are the products of combustion actually leaving the room? The analyser asks how well the appliance is burning. Neither answer stands in for the other.

How should the measurements be recorded?

At the appliance, while the analyser is still connected, with the readings alongside the commissioning data they were judged against. On a new boiler the destination is the Benchmark commissioning checklist, carrying CO and combustion ratio at maximum and minimum rate: HHIC boiler manufacturers have agreed that completing it is a condition of warranty, and because commissioning documentation is a Building Regulations requirement, Gas Safe Register will defect an installation where those figures are not correctly recorded. Copying figures into the van later, or off a curling thermal printout at home, is where transposed digits creep into combustion ratios, and that is not a small class of mistake. Manifold's FlueScan reads CO, CO₂ and the ratio straight off the analyser screen with the phone camera for you to confirm, so the numbers on the record are the numbers the analyser showed, and this year's readings sit next to last year's when the appliance's story needs telling.

Flue gas measurement is work for a competent, Gas Safe registered engineer using a calibrated analyser, judged against the appliance manufacturer's data and the current BS 7967 procedure. This guide is a refresher on measurement practice, not a substitute for either.

Frequently asked

Are my flue gas readings OK?

Judge them against the appliance manufacturer's published figures for that model first, because those are the reference and they vary by appliance. Where a maker gives no figure of its own, Gas Safe Register's TB 143 sets key action levels of CO at or below 350 ppm and a combustion ratio at or below 0.0040, measured at both maximum and minimum rate with the analyser settled.

What should the CO₂ reading be on a flue gas analyser?

Whatever the appliance's installation instructions say, and it differs by model and by rate. As published examples: Worcester Bosch gives CO₂ between 9.0 and 9.8% at maximum rated output and between 8.2 and 9.0% at minimum for the Greenstar 4000 combi on natural gas, while Vaillant's set values for the ecoTEC plus VU/VUW ..6/5-5 are 9.2 ± 1.0 Vol% at full load with the front casing closed. There is no universal figure to carry between appliances.

What is the maximum CO reading when commissioning a boiler?

TB 143's key action level, which applies where the manufacturer sets none of its own, is CO at or below 350 ppm alongside a combustion ratio at or below 0.0040. Manufacturers are often tighter: Worcester Bosch specifies a CO reading below 250 ppm at maximum and minimum rated output for the Greenstar 4000 combi, and the maker's figure is the one that governs.

Why won't my flue gas readings settle?

Usually because the appliance is not yet in the condition the test asks for, or the sample is not sealed. Give it the time the manual specifies: Worcester's Greenstar 4000 figures are read 10 minutes after firing and Vaillant's after at least five minutes at full load. Then check the probe seals the test point, and that the appliance can hold the rate rather than cycling on a low heating demand.

Why are my CO and CO₂ readings both low?

Suspect dilution. Air drawn into the sample lowers CO and CO₂ together, so both figures can look reassuring while telling you little; the ratio between them is largely unaffected, which is why it is the screening figure. An oxygen reading well above the manufacturer's data points the same way. Check the probe position and seal against the instructions, and sample again.

Can flue gas readings be taken from a chimney or open flue?

Yes, and BS 7967:2015 covers analyser use on open-flued (type B) appliances as well as flueless and room-sealed ones. Sample where that appliance's instructions direct, using the manufacturer's test point where one is provided; where there is no sampling point and no stated procedure, the manufacturers' flowchart says to ask them rather than improvise. Open flues make dilution more likely, which is exactly when the CO/CO₂ ratio matters most.

Spend less of your evening on this.

Manifold, the gas engineer app, does CP12s on the doorstep and chases the renewals for you. Start a free 30-day trial, no card required. In early access for UK gas engineers.

Start your free 30-day trial