IGEM/UP/1B Edition 4: what changes on 1 October 2026

By Jordan Valentine-Dunn, Gas Safe registered engineer · 28 September 2026

From 1 October 2026 every tightness test on a small natural gas, LPG or LPG/Air installation follows IGEM/UP/1B Edition 4, and Edition 3 is withdrawn on 30 September. The permissible drop now comes from the installation volume and the fuel gas, not the meter size, and movement within limits must be proved not to be the pipework.

A U-gauge manometer connected by a hose to the test point on a gas pipe, with the water column slightly uneven

When does Edition 4 become mandatory?

On 1 October 2026, in all circumstances, according to IGEM. For six months both editions ran side by side, and Gas Safe Register agreed not to defect a business at inspection for not yet being conversant with Edition 4. That period ends on 30 September.

The Edition 4 timeline, from IGEM's Edition 4 page, Gas Safe Register's ISU 133 (Edition 2) and the Registered Gas Engineer article of 11 May 2026
DateWhat happened
March 2026IGEM publishes IGEM/UP/1B Edition 4 (Communication 1903)
25 March 2026Gas Safe Register publishes the first ISU 133
15 April 2026ISU 133 Edition 2 issued, superseding the first after industry feedback
30 September 2026Edition 3 withdrawn; the six months of running both editions ends
1 October 2026Every tightness test in scope must follow Edition 4

What pressure drop is allowed under Edition 4?

It depends on the fuel gas and the installation volume (IV), and applies only with existing appliances connected and no smell of gas. With pipework only, or only new appliances, no perceptible movement is allowed.

Maximum permissible pressure drop by fuel gas and installation volume: IGEM/UP/1B Edition 4 tables 2, 3 and 5, as reproduced in Gas Safe Register's ISU 133 (Edition 2, 15 April 2026)
Fuel gas and tableInstallation volume (IV)Maximum permissible drop
Natural gas (table 3)Up to 0.005 m³8 mbar
Natural gas (table 3)Over 0.005 up to 0.010 m³4 mbar
Natural gas (table 3)Over 0.010 up to 0.015 m³2.5 mbar
Natural gas (table 3)Over 0.015 up to 0.035 m³1 mbar
LPG/Air (table 2)Up to 0.025 m³1.5 mbar
LPG/Air (table 2)Over 0.025 up to 0.035 m³0.5 mbar
LPG (table 5)Up to 0.0025 m³2 mbar
LPG (table 5)Over 0.0025 up to 0.005 m³1 mbar
LPG (table 5)Over 0.005 up to 0.01 m³0.5 mbar
LPG (table 5)Over 0.01 up to 0.035 m³No perceptible movement

IGEM's FAQ explains why a small installation may lose 8 mbar and a larger one only 1 mbar: every limit is based on a leakage rate of 19 ml per minute for the installation volume, so the two are roughly the same escape. The Registered Gas Engineer article says the LPG table is unchanged from previous versions.

What else changes in the procedure?

Edition 4 rules and how they compare with Edition 3, from ISU 133 (Edition 2), IGEM's Edition 4 FAQ and the Registered Gas Engineer article of 11 May 2026
RuleEdition 4, from 1 October 2026Compared with Edition 3
Permissible dropRead from the IV and the fuel gasChanged: it was based on the meter size alone
Movement within limitsIsolate the appliances and retest the pipework and meter; no perceptible movement allowedNew: confirming the drop was not on the pipework was not previously required
Purge volumePV = 1.5 x IV on every installation, so the IV is worked out whenever you purgeChanged: a PV of 0.01 m³ could be assumed for pipe up to 28 mm and a meter up to 6 m³/h
Low test pressureIf the test pressure cannot be reached, isolate and investigate; natural gas may be tested at 18 mbar minimum, with IGEM/G/13 operating pressure checks after a passNew note in Edition 4
No perceptible movement0.25 mbar or less on a fluid gauge or an electronic gauge; 0.2 mbar on an electronic gauge reading to one decimal placeStated in ISU 133; the published summaries do not say whether it changed
Smell of gasA fail whatever the gauge showsNot listed as a change; IGEM's FAQ states it
Record keepingGas Safe Register recommends recording which edition the test followedNew recommendation

How does a test work out in practice?

Two natural gas examples with existing appliances connected, after the let-by at 7 to 10 mbar for 1 minute, 1 minute to stabilise and the 2 minute test at 20 mbar. First, the water gauge drops 0.8 mbar. That is perceptible, but it is below 1 mbar, the smallest natural gas limit, so IGEM's FAQ says it is within limits without working out the IV. You still isolate the appliances and retest: any perceptible movement on the pipework is a fail.

Second, the gauge drops 3 mbar on an installation whose IV you work out at 0.012 m³. That band allows 2.5 mbar, so the test fails: trace and repair the escape or make the installation safe under IGEM/G/11. After the repair, the purge volume is 1.5 x 0.012 = 0.018 m³, which is under 0.02 m³, so natural gas may purge to air. LPG and LPG/Air always purge to ignition.

How is the installation volume worked out?

By adding the internal volume of the pipework, its fittings and the meter, from Appendix 7 of the standard, which IGEM sells rather than publishes. IGEM's scope examples show the size of 0.035 m³: 25 m of 35 mm copper with a U6 meter, or 10 m with a U16, both come in under it. Where pipe disappears into a wall, the Registered Gas Engineer article says to assume the largest visible size, so the IV is overestimated, never under.

Does Edition 4 cover every installation?

No. IGEM's scope is installation pipework with a nominal bore up to 35 mm, a meter badged up to 16 m³/h, an IV up to 0.035 m³, a maximum operating pressure at the emergency control valve up to 2 bar for natural gas and LPG/Air, and an operating pressure up to 21 mbar for natural gas and LPG/Air or 37 mbar for LPG. Above 0.035 m³, IGE/UP/1 applies. LPG service pipework is outside it.

This summarises published guidance, not the whole standard, which ISU 133 says engineers must know. Only a Gas Safe registered engineer may carry out a tightness test, or install, service or certify a gas appliance. If you smell gas, call the National Gas Emergency Service on 0800 111 999.

When you record the result, Manifold's check page carries the same Edition 4 calculator and saves the edition, fuel gas, IV, drop and result against the job, printed on the Landlord Gas Safety Record.

Frequently asked

Can I still test to IGEM/UP/1B Edition 3 after 30 September 2026?

No. IGEM withdraws Edition 3 on 30 September 2026 and Edition 4 is effective from 1 October 2026 in all circumstances. The Registered Gas Engineer article says that from 1 October every tightness test must be carried out to Edition 4.

What is the maximum permissible drop for natural gas under Edition 4?

It depends on the installation volume: 8 mbar up to 0.005 m³, 4 mbar up to 0.010 m³, 2.5 mbar up to 0.015 m³ and 1 mbar up to 0.035 m³. These apply only with existing appliances connected and no smell of gas.

Do I have to calculate the installation volume on every tightness test?

Not for the pass or fail when the drop is below the smallest limit for the fuel gas, 1 mbar for natural gas. IGEM's FAQ says the IV must still be calculated before any purge, because purge volume is 1.5 times the IV.

What counts as no perceptible movement on the gauge?

Gas Safe Register's ISU 133 treats 0.25 mbar or less as not perceptible on a fluid gauge and on an electronic gauge, and 0.2 mbar or less on an electronic gauge that reads to one decimal place.

If a test fails under Edition 4, can I retest it under Edition 3?

No. The Registered Gas Engineer article says a failed Edition 4 test cannot be passed by retesting to the old procedure; trace and repair the escape or make safe under IGEM/G/11, and record which edition you used.

Can an appliance with a small drop stay connected?

Yes, if the pipework retest shows no perceptible movement, the drop is within the limit for the IV, there is no smell of gas, and a site-specific risk assessment deems it satisfactory, according to the Registered Gas Engineer article.