Boiler combustion figures by brand: CO₂, CO and ratio at commissioning
The manufacturer's commissioning data for that model is the reference, and Gas Safe TB 143's key action levels, CO at or below 350 ppm and a combustion ratio at or below 0.0040, are the fallback where a maker sets none. Figures differ by make, model, rate and fuel, so this page lists them per make from the installation manuals.
Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed September 2026
Readings are judged against the manufacturer's commissioning data for the appliance in front of you, and the tables below transcribe that data make by make, with the manual's document number and revision under each one. Use them to check a reading when the book is in the loft; where they differ from the current manual, the manual wins.
Why do the figures differ by make?
Because each maker sets its own air-to-gas balance for the appliance it built, and the CO₂ percentage is a direct read-out of that balance. The burner, the fan curve, the gas valve and the heat exchanger all differ, so a CO₂ figure that means correct combustion on one boiler means a lean or a rich mixture on another. Rate moves it as well, which is why every manual gives a maximum-rate figure and most give a separate minimum-rate one. Fuel moves it most of all: propane carries more carbon per unit of gas, so its CO₂ figures sit a percentage point or more above the natural gas figures for the same appliance.
TB 143 sits underneath all of it. Gas Safe Register's bulletin says the boiler manufacturer's guidance must be followed where it is available, and that makers may choose to give their own specific action levels for CO and combustion ratio in their instructions. Where none is given, manufacturers have agreed that CO at or below 350 ppm with a combustion ratio at or below 0.0040 will ensure the boiler can be considered safe. Every table below is one maker's layer sitting on top of that floor.
What are Worcester Bosch's combustion figures?
Worcester publishes a CO₂ window for each rate rather than a single value, and on the Greenstar 4000 it also asks the minimum-rate reading to step down by at least 0.2 from the maximum-rate reading you actually took. Both ranges below are read in chimney sweep mode with the combustion chamber cover on.
| Range | CO₂ at maximum rate | CO₂ at minimum rate | CO limit | Combustion ratio | Flue integrity at the air inlet point | Test conditions | LPG figures |
|---|---|---|---|---|---|---|---|
| Greenstar 4000 combi (GR4700iW C) | 9.0 to 9.8% on natural gas. | 8.2 to 9.0%, and at least 0.2 below the maximum reading taken. | Under 250 ppm at both rates. | Below 0.004 at both rates (commissioning flowchart). | O₂ 20.6% or above and CO₂ below 0.2%, casing fitted. | Chimney sweep mode, cover on. CO₂ read 10 minutes after firing. | Maximum 10.4 to 11.0%; minimum 10.0 to 10.4% and at least 0.2 below the maximum taken. CO under 250 ppm. |
| Greenstar 8000 Life combi (GR8300iW 30 to 50 C) | 9.5% ± 0.4 on natural gas, O₂ 4.0%. | 8.6% ± 0.4, O₂ 5.5%. | Under 250 ppm at maximum, under 75 ppm at minimum. | Below 0.004 at both rates (commissioning flowchart). | O₂ 20.6% or above and CO₂ below 0.2%. | Chimney sweep mode, maximum then minimum. Technical data quotes CO₂ after 10 minutes. | Propane: maximum 10.8% ± 0.4, O₂ 4.6%; minimum 10.2% ± 0.4, O₂ 5.5%. CO under 250 ppm, then under 75 ppm. |
What are Vaillant's combustion figures?
Vaillant publishes its set values at full load only, and gives two CO₂ figures for the same appliance: one with the front casing closed and one with it removed. It also publishes its own CO ceiling and its own combustion ratio, both tighter than TB 143's, so on these boilers the maker's numbers are the ones that govern.
| Range | CO₂ at maximum rate | CO₂ at minimum rate | CO limit | Combustion ratio | Flue integrity at the air inlet point | Test conditions | LPG figures |
|---|---|---|---|---|---|---|---|
| ecoTEC plus VU, VUW ..6/5-5 | Natural gas H: 9.2 ± 1.0 Vol% casing closed, 9.0 ± 1.0 Vol% casing removed. | None published; the set values are full load figures. | 250 ppm or less at full load. | 0.0031 or less on natural gas H. | O₂ 20.6% or above and CO₂ below 0.2% (commissioning flowchart). | Check programme P.01, read after at least five minutes at full load. O₂ 4.5 ± 1.8 Vol% casing closed. Wobbe index 14.09 kWh/m³. | LPG P: CO₂ 10.4 ± 0.5 Vol% casing closed, 10.2 ± 0.5 removed. O₂ 5.1 ± 0.8 Vol%. CO 250 ppm or less, ratio 0.0026 or less. Wobbe 21.34 kWh/m³. |
| ecoTEC pro VUW ..6/5-3 | Natural gas H: 9.2 ± 1.0 Vol% casing closed, 9.0 ± 1.0 Vol% casing removed. | None published. | 250 ppm or less at full load. | 0.0031 or less on natural gas H. | O₂ 20.6% or above and CO₂ below 0.2%. | Check programme P.01, read after at least five minutes at full load. O₂ 4.5 ± 1.8 Vol% casing closed. | LPG P: CO₂ 10.4 ± 0.5 Vol% casing closed, 10.2 ± 0.5 removed. O₂ 5.1 ± 0.8 Vol%. CO 250 ppm or less, ratio 0.0026 or less. |
What are Baxi's combustion figures?
Baxi gives a nominal CO₂ with a tolerance range either side, an O₂ figure alongside it and a CO ceiling, all measured with the frontal panel closed. The natural gas numbers hold across every output size in these two ranges. The propane numbers do not, and the 36 kW 600 Combi 2 carries its own pair. CO appears twice in each manual: the service settings table allows under 400 ppm, but the commissioning flowchart passes the boiler only at under 350 ppm with a ratio below 0.004, so commission to the lower figure.
| Range | CO₂ at maximum rate | CO₂ at minimum rate | CO limit | Combustion ratio | Flue integrity at the air inlet point | Test conditions | LPG figures |
|---|---|---|---|---|---|---|---|
| 600 Combi 2 (24, 30, 36) | G20 nominal 9.0%, tolerance 8.8 to 9.4%. O₂ 4.8% (5.2 to 4.1). | G20 nominal 8.5%, tolerance 8.1 to 8.6%. O₂ 5.7% (6.5 to 5.6). | Under 350 ppm at both rates in the commissioning flowchart. The service settings table gives CO max under 400 ppm. | Below 0.004 at both rates (commissioning flowchart). The servicing section repeats it. | O₂ 20.6% or above and CO₂ below 0.2%. | Chimney sweep function: L minimum, h maximum in heating, H maximum in hot water. Combustion allowed to stabilise, no fixed waiting time given. Gas valve check values 8.8 to 9.4% and 8.1 to 8.6%. | G31 propane, 24 and 30: 10.3% (10.2 to 10.7) maximum, 9.7% (9.2 to 9.8) minimum. On the 36: 10.0% (10.0 to 10.5) and 9.6% (9.2 to 9.8). Table CO max under 400 ppm; the commissioning flowchart asks for under 350 ppm. |
| 800 System 2 (18, 24, 30) | G20 nominal 9.0%, tolerance 8.8 to 9.4%. O₂ 4.8% (5.2 to 4.1). | G20 nominal 8.5%, tolerance 8.1 to 8.6%. O₂ 5.7% (6.5 to 5.6). | Under 350 ppm at both rates in the commissioning flowchart. The service settings table gives CO max under 400 ppm. | Below 0.004 at both rates (commissioning flowchart). | O₂ 20.6% or above and CO₂ below 0.2%. | Chimney sweep function, frontal panel closed, combustion allowed to stabilise before the probe goes in. | G31 propane: 10.3% (10.2 to 10.7) maximum, 9.7% (9.2 to 9.8) minimum. O₂ 5.2% (5.4 to 4.6) and 6.1% (6.9 to 6.0). Table CO max under 400 ppm; the commissioning flowchart asks for under 350 ppm. |
What are Ideal's combustion figures?
Ideal puts its CO₂ content in Table 1 of the General Data at the front of the manual, quoted at maximum and at minimum with a ± 0.7 tolerance, and the figure changes with the output size within a range. Both manuals below give Table 1 for natural gas only, at 2H, G20, 20 mbar.
| Range | CO₂ at maximum rate | CO₂ at minimum rate | CO limit | Combustion ratio | Flue integrity at the air inlet point | Test conditions | LPG figures |
|---|---|---|---|---|---|---|---|
| Logic Max Combi2 (C24, C30, C35) | Max. DHW: C24 9.2%, C30 9.3%, C35 9.7%, each ± 0.7. | Min. CH: C24 8.5%, C30 8.5%, C35 8.8%, each ± 0.7. | Below 350 ppm at both rates (commissioning flowchart). | Below 0.0040 at both rates. Above 0.004 the servicing schedule sends you to the cleaning procedure. | O₂ 20.6% or above, or CO₂ 0.2% or below, where an air inlet test point is provided. | Maximum DHW rate and minimum rate each held for 10 minutes from the menu. Probe stays out of the flue while combustion stabilises. | Table 1 is quoted for 2H, G20, 20 mbar only. No separate propane CO₂ figures are given. |
| Vogue Max Combi (26, 32, 40) | Max. DHW: 26 is 9.4%, 32 is 9.8%, 40 is 9.6%, each ± 0.7. | Min. DHW: 26 is 8.0%, 32 is 8.5%, 40 is 8.1%, each ± 0.7. | Below 350 ppm at both rates. | Below 0.0040 at both rates. | O₂ 20.6% or above, or CO₂ 0.2% or below. | Maximum then minimum rate, readings allowed to stabilise before recording. | Table 1 is quoted for 2H, G20, 20 mbar only. |
What are Glow-worm's combustion figures?
Glow-worm gives one CO₂ check value per appliance, read in check programme P.01 with the setting value at 100, which is maximum heat input, and the same figure applies whether the front casing is removed or installed. The Essential manual adds its own full-load limits, CO at or below 250 ppm and a combustion ratio at or below 0.0027, both tighter than TB 143's. The Energy7 and Energy 2 manuals set no appliance limits of their own, so TB 143's levels are the ones to work to there. The Benchmark checklist still asks for CO, CO₂ and the ratio at maximum and, where possible, minimum rate.
| Range | CO₂ at maximum rate | CO₂ at minimum rate | CO limit | Combustion ratio | Flue integrity at the air inlet point | Test conditions | LPG figures |
|---|---|---|---|---|---|---|---|
| Energy7 25c, 30c, 35c -A (H-GB) | 9.2 ±1% on natural gas H, casing removed or installed. | None published; the check is made at maximum heat input. | None published. TB 143's 350 ppm applies. | None published. TB 143's 0.0040 applies. | On extended flue installations the air analysis point is used to check for flue gas recirculation and for unusual CO or CO₂ in the supply air. No numeric limits given. | Check programme P.01 set to 100, waiting period 5 minutes for a stable value. | See the Energy 2 30c P row. |
| Essential 24c, 28c | 9.2 ±1% on natural gas G20, casing removed or installed. If it has to be set, 9.2 ±0.2% at full load (value with the front casing removed). | None published. | 250 ppm or less at full load (section 11.4). The commissioning flow chart in the appendix asks for under 350 ppm at both rates. | 0.0027 or less at full load (section 11.4). The flow chart asks for under 0.004 at both rates. | O₂ 20.6% or above and CO₂ below 0.2% (commissioning flow chart). The air analysis point is used for the flue gas recirculation check, strongly recommended where the flue is longer than 2 m. | Check programme P.01 set to 100, waiting period 5 minutes for a stable value. O₂ 4.5 ±1.8 vol% at full load. | None. The manual says these products are only designed for natural gas systems. |
| Energy 2 30c P (LPG) | 10.1 ±1.0 vol% casing removed, 10.3 ±1.0 vol% casing fitted. | None published. | No appliance figure. The commissioning flow chart in the appendix asks for under 350 ppm at both rates, TB 143's level. | No appliance figure. The flow chart asks for under 0.004 at both rates. | O₂ 20.6% or above and CO₂ below 0.2% (commissioning flow chart). On extended flue installations the air analysis point is used for the recirculation check. | Check programme P.01 set to 100, waiting period 5 minutes. | The figures in this row are the propane ones. |
Combustion checking is work for a competent, Gas Safe registered engineer using a calibrated analyser of the correct type. The installation manual for the appliance in front of you is the reference; this page is a transcription of published data, and where it differs from the current manual, the manual wins.
How do I use these figures on site?
In TB 143's order: maximum rate first, then minimum, judging each settled reading against the manual for that appliance and recording both sets on the Benchmark checklist. Set the boiler to maximum in whatever test mode it has, leave the probe out of the flue while the combustion settles, take the air inlet reading to prove flue integrity, then move to the flue gas point and let the figures stabilise before you write anything down. Drop to minimum and repeat.
The tables are for checking a reading, not for setting one. On every appliance here the air/gas ratio valve is factory set, and TB 143 and the manuals agree on what to do about that during commissioning, which is nothing, unless the maker's technical line has told you otherwise. Where a maker's figure is tighter than TB 143's, as Vaillant's 250 ppm and 0.0031 and the Glow-worm Essential's 250 ppm and 0.0027 are, the maker's figure is the one to work to.
Use these with
What if my reading is outside the maker's figure?
Work the flowchart in that appliance's instructions rather than reaching for the gas valve. Our guide on analyser readings walks the common patterns and what each one points at, and the flue gas analysis guide carries the wider procedure. What the manuals here have in common is the order they send you in: check the seals around the burner and the internal flue, door and case seals, confirm flue integrity, confirm the inlet pressure and the gas rate, then retest. If the readings are still outside the figures, the appliance goes off and that maker's technical helpline gets the call before it goes back into service.
Once the readings are inside the maker's figures, they still have to survive the trip to the record. Manifold's FlueScan reads CO, CO₂ and the ratio straight off the analyser screen with the phone camera for you to confirm at the appliance, so the numbers that reach the commissioning record are the numbers the analyser showed, and next year's service sits next to this year's when the appliance's history matters.
Frequently asked
Sources
- Gas Safe Register, TB 143: CO and combustion ratio checks on boiler commissioning
- Worcester Bosch, Greenstar 4000 combi installation and maintenance instructions (6 720 891 161, 2021/10)
- Worcester Bosch, Greenstar 8000 Life combi installation and maintenance instructions (6720883865, 2021/11)
- Vaillant, ecoTEC plus VU, VUW ..6/5-5 installation and maintenance instructions (0020244997_07)
- Vaillant, ecoTEC pro VUW ..6/5-3 installation and maintenance instructions (0020209589_05)
- Baxi, 600 Combi 2 installation and service manual (7796561 - 03, 4/23)
- Baxi, 800 System 2 installation and service manual (7821598 - 03, 8/23)
- Ideal Heating, Logic Max Combi2 installation and servicing (UIN 237660 A05, 11/2025)
- Ideal Heating, Vogue Max Combi installation and servicing (UIN 222378 A08, 09/2023)
- Glow-worm, Energy7 combi installation and maintenance instructions (0020300875_01)
- Glow-worm, Essential combi installation and maintenance instructions (0020206373_04)
- Glow-worm, Energy 2 30c P (LPG) installation and maintenance instructions (0020283671_04)
- HHIC, Benchmark gas boiler commissioning checklist
- Gas Safe Register