Boiler cupboard clearances by make
Each maker prints its own cupboard clearances. In the five current combi manuals read for this guide, the sides need 2.5 to 5 mm, below the boiler 100 to 186 mm, and in front 450 to 600 mm for servicing. Work to the manual for the boiler fitted, not another make's figure.
Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed November 2026
A boiler in a cupboard has to leave room for the case to come off, for the engineer to work and for air to move. The makers print those spaces in millimetres, and no two of them agree. The tables below set five current combi ranges side by side, each from the maker's own installation manual.
What clearance does each boiler need around it?
| Range | Each side | Above | Below | In front |
|---|---|---|---|---|
| Worcester Bosch Greenstar 4000 combi | 5 | 170 with a 60/100 flue, 210 with an 80/125 flue | 186 | 600, or 450 if the manual's reduced front conditions are met; 20 from the appliance to a removable door |
| Vaillant ecoTEC plus | 5 (optimum about 50) | 165 with a 60/100 flue, 275 with an 80/125 flue | 180 (optimum about 250) | 500, which may be provided by an opening door |
| Ideal Logic Combi2 | 2.5 | Not given in the manual's clearance text | 100 for servicing, reducible to 5 after installation if an easily removable panel gives the 100 | 5 from the cupboard door, with 450 overall and the door open |
| Baxi 600 Combi 2 | 2.5 | 178, as printed on fig.15 | 150 | 450 for servicing, 5 in operation |
| Glow-worm Energy7 | 5 (70 if the side sections ought to be removed) | 150 for a top air/flue connection, 20 for a rear one | 150 | 600 |
Baxi prints its figures as minimum recommended dimensions that include case removal, spanner access and air movement. Worcester Bosch adds a caution that the appliance will overheat if the space around it is restricted, and says not to add cupboards or shelves next to or around it.
Does a boiler in a cupboard need ventilation?
| Range | What the manual says |
|---|---|
| Worcester Bosch Greenstar 4000 combi | Follow BS 6798 and BS 5440, keep the minimum clearances and fit an access door. In an unventilated airing or storage cupboard no partition is needed between the appliance and the storage space if the clearances are kept. |
| Vaillant ecoTEC plus | Compartment ventilation is not required, as the boiler is only certified with a concentric flue. No clearance is needed to combustible materials beyond the minimum clearances. |
| Ideal Logic Combi2 | A boiler in a compartment does not require ventilation but must have adequate clearances for servicing and a suitable label. The compartment must not be used for storage. |
| Baxi 600 Combi 2 | Where the boiler is in a cupboard or compartment, no air vents are required, and it runs sufficiently cool without ventilation. |
| Glow-worm Energy7 | Compartment ventilation is not required. A 5 mm clearance must be kept around the flue's air intake where it passes through combustible material. |
How do you check a cupboard against a manual?
Add the boiler's own size to the clearances on each side, then leave the working space in front. Two examples from the figures above.
| Example | Working | Result |
|---|---|---|
| Greenstar 4000 combi with a 60/100 flue | Width 400 + 5 + 5 = 410. Height 724 + 170 above + 186 below = 1,080. Depth 310 + 20 to the door = 330. | The manual's overall clearance width is 410, height 1,080 and compartment depth 330. Leave 600 in front, or 450 under the reduced front conditions. |
| Logic Combi2 behind a cupboard door | Width 395 + 2.5 + 2.5 = 400. Height 700 + 100 below for servicing = 800 before any top clearance. | The cupboard must be at least 400 wide inside. Ideal allows the base 5 from the boiler only if a removable panel gives the 100 for servicing, and still wants 450 overall in front with the door open. |
Why do two Glow-worm manuals give different front clearances?
The figure belongs to the manual, not the maker. Glow-worm's Energy7 manual prints 600 mm in front. Its Easicom 3 manual prints at least 500 mm, with 5 mm for a cupboard installation, and 150 mm above and below. Vaillant's ecoTEC plus manual prints 500 in front. Use the manual for the exact range, and note the revision on the job record.
Only a Gas Safe registered engineer can size, install, service or certify a boiler, and whether a particular cupboard is acceptable is their call from the manual for that model and the current regulations. This page reports what the five manuals print, not a rule for every model of a range.
What about a cupboard in a bedroom or bathroom?
A cupboard in a bedroom or bathroom brings regulation 30 into play as well as the maker's clearances, because a cupboard that vents into such a room counts as the room. The bedroom and bathroom guide sets that out. If you suspect carbon monoxide, turn the appliance off and call National Gas on 0800 111 999, free, at any hour.
On a Manifold gas safety check each appliance is recorded with its location and flue type, and the record lists every appliance on the visit.
Read next
Frequently asked
Sources
- Worcester Bosch, Greenstar 4000 combi installation manual (6720891161, 2021/10), section 4.3.3
- Vaillant, ecoTEC plus installation and maintenance instructions (0020244997_07), section 6.4
- Ideal Heating, Logic Combi2 C24, C30, C35 installation and servicing manual (UIN 237664 A08), section 1.15
- Baxi, 600 Combi 2 installation and servicing manual, sections 5.4.3 and 5.4.5
- Glow-worm, Energy7 combi installation and maintenance instructions (0020300875_01), sections 6.5 and 6.6
- Glow-worm, Easicom 3 installation and maintenance instructions (0020239562_05), section 6.4
- National Gas, emergency contacts
Related guides
Last reviewed November 2026. This guide is general information, not legal or safety advice, gas safety work must be carried out by an appropriately Gas Safe registered engineer. Rules can change, so check the linked official sources for the current position.