Boiler cupboard clearances by make

Each maker prints its own cupboard clearances. In the five current combi manuals read for this guide, the sides need 2.5 to 5 mm, below the boiler 100 to 186 mm, and in front 450 to 600 mm for servicing. Work to the manual for the boiler fitted, not another make's figure.

Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed November 2026

A boiler in a cupboard has to leave room for the case to come off, for the engineer to work and for air to move. The makers print those spaces in millimetres, and no two of them agree. The tables below set five current combi ranges side by side, each from the maker's own installation manual.

What clearance does each boiler need around it?

Minimum clearances in mm for one current combi range per make: Worcester Bosch Greenstar 4000 (6720891161, table 11), Vaillant ecoTEC plus (0020244997_07, section 6.4), Ideal Logic Combi2 (UIN 237664 A08, section 1.15), Baxi 600 Combi 2 (section 5.4.5) and Glow-worm Energy7 (0020300875_01, section 6.5)
RangeEach sideAboveBelowIn front
Worcester Bosch Greenstar 4000 combi5170 with a 60/100 flue, 210 with an 80/125 flue186600, or 450 if the manual's reduced front conditions are met; 20 from the appliance to a removable door
Vaillant ecoTEC plus5 (optimum about 50)165 with a 60/100 flue, 275 with an 80/125 flue180 (optimum about 250)500, which may be provided by an opening door
Ideal Logic Combi22.5Not given in the manual's clearance text100 for servicing, reducible to 5 after installation if an easily removable panel gives the 1005 from the cupboard door, with 450 overall and the door open
Baxi 600 Combi 22.5178, as printed on fig.15150450 for servicing, 5 in operation
Glow-worm Energy75 (70 if the side sections ought to be removed)150 for a top air/flue connection, 20 for a rear one150600

Baxi prints its figures as minimum recommended dimensions that include case removal, spanner access and air movement. Worcester Bosch adds a caution that the appliance will overheat if the space around it is restricted, and says not to add cupboards or shelves next to or around it.

Does a boiler in a cupboard need ventilation?

What each manual says about cupboards and compartments, from the same five manuals
RangeWhat the manual says
Worcester Bosch Greenstar 4000 combiFollow BS 6798 and BS 5440, keep the minimum clearances and fit an access door. In an unventilated airing or storage cupboard no partition is needed between the appliance and the storage space if the clearances are kept.
Vaillant ecoTEC plusCompartment ventilation is not required, as the boiler is only certified with a concentric flue. No clearance is needed to combustible materials beyond the minimum clearances.
Ideal Logic Combi2A boiler in a compartment does not require ventilation but must have adequate clearances for servicing and a suitable label. The compartment must not be used for storage.
Baxi 600 Combi 2Where the boiler is in a cupboard or compartment, no air vents are required, and it runs sufficiently cool without ventilation.
Glow-worm Energy7Compartment ventilation is not required. A 5 mm clearance must be kept around the flue's air intake where it passes through combustible material.

How do you check a cupboard against a manual?

Add the boiler's own size to the clearances on each side, then leave the working space in front. Two examples from the figures above.

Two worked checks, using the manuals' own dimensions
ExampleWorkingResult
Greenstar 4000 combi with a 60/100 flueWidth 400 + 5 + 5 = 410. Height 724 + 170 above + 186 below = 1,080. Depth 310 + 20 to the door = 330.The manual's overall clearance width is 410, height 1,080 and compartment depth 330. Leave 600 in front, or 450 under the reduced front conditions.
Logic Combi2 behind a cupboard doorWidth 395 + 2.5 + 2.5 = 400. Height 700 + 100 below for servicing = 800 before any top clearance.The cupboard must be at least 400 wide inside. Ideal allows the base 5 from the boiler only if a removable panel gives the 100 for servicing, and still wants 450 overall in front with the door open.

Why do two Glow-worm manuals give different front clearances?

The figure belongs to the manual, not the maker. Glow-worm's Energy7 manual prints 600 mm in front. Its Easicom 3 manual prints at least 500 mm, with 5 mm for a cupboard installation, and 150 mm above and below. Vaillant's ecoTEC plus manual prints 500 in front. Use the manual for the exact range, and note the revision on the job record.

Only a Gas Safe registered engineer can size, install, service or certify a boiler, and whether a particular cupboard is acceptable is their call from the manual for that model and the current regulations. This page reports what the five manuals print, not a rule for every model of a range.

What about a cupboard in a bedroom or bathroom?

A cupboard in a bedroom or bathroom brings regulation 30 into play as well as the maker's clearances, because a cupboard that vents into such a room counts as the room. The bedroom and bathroom guide sets that out. If you suspect carbon monoxide, turn the appliance off and call National Gas on 0800 111 999, free, at any hour.

On a Manifold gas safety check each appliance is recorded with its location and flue type, and the record lists every appliance on the visit.

Frequently asked

How much space does a Worcester Bosch Greenstar 4000 need in a cupboard?

Worcester's manual gives an overall clearance width of 410 mm, height of 1,080 mm with a 60/100 flue and 1,120 mm with an 80/125 flue, 186 mm below, 5 mm each side and 450 or 600 mm in front.

Can a boiler sit in an airing cupboard with towels stored in it?

Worcester says do not store combustible materials on or next to the appliance, such as clothes or towels, and Ideal says its compartment must not be used for storage. Both are manual rules, so check the one for the boiler fitted.

Does a combi boiler in a cupboard need an air vent?

Not according to the Vaillant, Ideal, Baxi and Glow-worm manuals read for this guide, which each say compartment ventilation is not required. Worcester's manual asks for the minimum clearances and an access door instead.

What is the smallest gap allowed at the side of a boiler?

The five manuals print 2.5 mm for Ideal and Baxi and 5 mm for Worcester Bosch, Vaillant and Glow-worm. Glow-worm asks for 70 mm if the side sections ought to be removed, and Vaillant gives about 50 mm as optimum.

Can the front clearance be reduced below 600 mm?

Worcester allows 450 mm in front if the case sits 1,000 to 1,500 mm off the floor, 186 mm is clear below, and 300 mm is clear on one side. Ideal and Baxi print 450 mm for servicing.

Are the clearances the same for every model in a range?

No. The figures here are from one manual per range, and flue type, model size and the manual's revision all change them. Read the installation manual for the exact model and keep the revision on the job record.