Boiler expansion vessel pressure by make

It depends on the maker. In five current combi manuals the built-in vessel is pre-charged to 0.75 bar (Worcester Bosch, Ideal) or 1.0 bar (Baxi), and Vaillant and Glow-worm say to top it up below 0.75 bar. The manuals that give a method read it at the vessel valve with the boiler drained.

Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed November 2026

The expansion vessel's air charge is set against the height of the system, and the cold fill pressure is set against the charge. The makers print both figures, and they differ by make. The tables below set five current combi ranges side by side, each from the maker's own installation manual.

What is each boiler's expansion vessel charged to?

Built-in expansion vessel and fill pressure for one current combi range per make: Worcester Bosch Greenstar 4000 (6720891161), Vaillant ecoTEC plus (0020244997_07), Ideal Logic Combi2 (UIN 237664 A08), Baxi 600 Combi 2 (7745721) and Glow-worm Energy7 (0020300875_01)
RangeVessel sizeFactory pre-chargeCold fill pressure
Worcester Bosch Greenstar 4000 combi6 litres0.75 bar0.8 to 1.7 bar when filling; system pressure 0.1 to 0.25 bar above the vessel pre-charge
Vaillant ecoTEC plus10 litresNot printed in the manual; top up if below 0.75 barAt least 0.8 bar, and at least 0.2 bar above the vessel's pressure
Ideal Logic Combi28 litres0.75 bar (the sizing table gives a vessel charge of 0.5 to 0.75 bar)Fill until the gauge reads 1 bar
Baxi 600 Combi 2Not printed in the manual; suitable for systems up to 100 litres1.0 barMinimum 1.0 bar cold; 1.0 to 1.5 bar at commissioning
Glow-worm Energy7Not printed in the manual's technical dataNot printed; top up if below 0.75 bar, to suit the static height1.0 to 1.5 bar

Worcester Bosch and Baxi both call for an extra vessel on systems over 100 litres, and Worcester adds one where the pressure would pass 2.5 bar at maximum temperature, fitted in the heating return close to the boiler and charged to match the built-in vessel. Ideal prints two figures in one manual: an initial charge of 0.75 bar in section 1.16, and a vessel charge of 0.5 to 0.75 bar in its sizing table.

How do you check the expansion vessel pressure?

Take the water pressure off the vessel first, then read the air side with a gauge at the vessel's valve. A reading taken with the system full shows the water pressure, not the charge. Each manual's own steps follow.

How each manual says to check or recharge the built-in vessel, from the same five manuals
RangeWhat the manual says
Worcester Bosch Greenstar 4000 combiA Schrader valve on the vessel allows the pressure to be adjusted. Where water has to be added often with no leak found, carry out an expansion vessel check. The manual gives no step list for the check.
Vaillant ecoTEC plusClose the service valves and drain the product, then measure at the vessel valve. Below 0.75 bar, top up, ideally with nitrogen, otherwise air, with the drain valve open. Water from the valve means the vessel is replaced.
Ideal Logic Combi2Remove the charge point cover, recharge to 0.75 bar, then check the boiler in hot water and heating modes. A note in section 3.2 says the boiler must be drained to replace components in sections 3.20 to 3.31; the recharging steps do not mention draining.
Baxi 600 Combi 2With the system cold, relieve the pressure by draining the boiler and check at the valve under the vessel. Adjust and repressurise. Check the pre-charge every year and restore it to 1 bar if necessary.
Glow-worm Energy7Section 12.13 drains the product, and 12.14 then measures at the vessel valve. Below 0.75 bar, top up to suit the static height, ideally with nitrogen, otherwise air, with the drain valve open. Water from the valve means the vessel is replaced.

How do you work out the right pre-charge?

From the static head. Worcester Bosch counts 0.1 bar per metre, measured from the vessel to the top of the highest radiator, and Glow-worm says the charge must not be less than that static head. Two worked examples using the manuals' own rules and tables.

Two worked examples, from Worcester's static head rule and Ideal's table 4 vessel sizing
ExampleWorkingResult
Greenstar 4000, highest radiator 9 m above the vessel9 m x 0.1 bar = 0.9 bar static head, above the 0.75 bar default. Choosing the manual's 1.0 bar curve, the system is set 0.1 to 0.25 bar higher.Vessel at 1.0 bar, system filled to 1.1 to 1.25 bar, and the curve read for system volume and flow temperature to see if an extra vessel is needed.
Logic Combi2 on a 125 litre systemTable 4 needs 7.8 litres of vessel with no system pre-pressurisation, or 9.2 litres if the system is pre-pressurised to 1.0 bar.The 8 litre vessel covers the first case. In the second an extra vessel goes on the return to the boiler, as section 1.16 says.

What does it mean if the pressure keeps rising?

Worcester Bosch's system gassing flow chart (fig. 103) starts there. If the pressure climbs above 2.5 bar when the boiler is on, it asks whether the vessel is charged higher than expected; if it is not, whether the charge is too low, and if so, re-pressurise the vessel. If the charge is correct, check the vessel is sized for the system. A pressure that keeps falling with a dripping relief valve points it at the valve instead.

Only a Gas Safe registered engineer can size, install, service or certify a boiler, and the vessel sits inside the case. This page reports what five manuals print for one range each; the manual for the exact model fitted governs, and a cylinder's own vessel follows the cylinder maker's manual.

An unvented cylinder carries its own expansion vessel or air volume, set by the cylinder maker, and the G3 guide covers that. Manifold produces the gas service record from the check you complete on your phone at the property.

Frequently asked

What should a combi boiler expansion vessel be set to?

The maker's figure for the model. Worcester Bosch's Greenstar 4000 and Ideal's Logic Combi2 leave the factory at 0.75 bar and Baxi's 600 Combi 2 at 1.0 bar. Glow-worm adds that the charge must not be less than the system's static head.

Can you check expansion vessel pressure with the system full?

No. Vaillant says to close the service valves and drain the product before measuring, and Baxi says to relieve the pressure by draining the boiler with the system cold. With water pressure on it the gauge does not read the air charge.

Should an expansion vessel be topped up with air or nitrogen?

Vaillant and Glow-worm both say ideally nitrogen, otherwise air, with the drain valve open while topping up. Worcester Bosch fits a Schrader type valve to its vessel to allow the pressure to be adjusted if required.

What does water coming out of the expansion vessel valve mean?

The vessel's diaphragm has let water through. Vaillant and Glow-worm both say that if water escapes from the valve of the expansion vessel, the expansion vessel must be replaced rather than recharged.

When does a system need an additional expansion vessel?

Worcester Bosch says over 100 litres of system volume or above 2.5 bar at maximum heating temperature, and Baxi says over 100 litres. Ideal's table 4 gives the vessel volume needed for each system size and pre-pressure.

How often should the expansion vessel be checked?

Baxi's manual says to check the pre-charge every year. Vaillant lists it in its maintenance table at regular intervals, and Worcester Bosch asks for a check whenever water is added often with no leak found.