Boiler expansion vessel pressure by make
It depends on the maker. In five current combi manuals the built-in vessel is pre-charged to 0.75 bar (Worcester Bosch, Ideal) or 1.0 bar (Baxi), and Vaillant and Glow-worm say to top it up below 0.75 bar. The manuals that give a method read it at the vessel valve with the boiler drained.
Reviewed by Jordan Valentine-Dunn, Gas Safe registered engineer · Portsmouth Gas Heating · Last reviewed November 2026
The expansion vessel's air charge is set against the height of the system, and the cold fill pressure is set against the charge. The makers print both figures, and they differ by make. The tables below set five current combi ranges side by side, each from the maker's own installation manual.
What is each boiler's expansion vessel charged to?
| Range | Vessel size | Factory pre-charge | Cold fill pressure |
|---|---|---|---|
| Worcester Bosch Greenstar 4000 combi | 6 litres | 0.75 bar | 0.8 to 1.7 bar when filling; system pressure 0.1 to 0.25 bar above the vessel pre-charge |
| Vaillant ecoTEC plus | 10 litres | Not printed in the manual; top up if below 0.75 bar | At least 0.8 bar, and at least 0.2 bar above the vessel's pressure |
| Ideal Logic Combi2 | 8 litres | 0.75 bar (the sizing table gives a vessel charge of 0.5 to 0.75 bar) | Fill until the gauge reads 1 bar |
| Baxi 600 Combi 2 | Not printed in the manual; suitable for systems up to 100 litres | 1.0 bar | Minimum 1.0 bar cold; 1.0 to 1.5 bar at commissioning |
| Glow-worm Energy7 | Not printed in the manual's technical data | Not printed; top up if below 0.75 bar, to suit the static height | 1.0 to 1.5 bar |
Worcester Bosch and Baxi both call for an extra vessel on systems over 100 litres, and Worcester adds one where the pressure would pass 2.5 bar at maximum temperature, fitted in the heating return close to the boiler and charged to match the built-in vessel. Ideal prints two figures in one manual: an initial charge of 0.75 bar in section 1.16, and a vessel charge of 0.5 to 0.75 bar in its sizing table.
How do you check the expansion vessel pressure?
Take the water pressure off the vessel first, then read the air side with a gauge at the vessel's valve. A reading taken with the system full shows the water pressure, not the charge. Each manual's own steps follow.
| Range | What the manual says |
|---|---|
| Worcester Bosch Greenstar 4000 combi | A Schrader valve on the vessel allows the pressure to be adjusted. Where water has to be added often with no leak found, carry out an expansion vessel check. The manual gives no step list for the check. |
| Vaillant ecoTEC plus | Close the service valves and drain the product, then measure at the vessel valve. Below 0.75 bar, top up, ideally with nitrogen, otherwise air, with the drain valve open. Water from the valve means the vessel is replaced. |
| Ideal Logic Combi2 | Remove the charge point cover, recharge to 0.75 bar, then check the boiler in hot water and heating modes. A note in section 3.2 says the boiler must be drained to replace components in sections 3.20 to 3.31; the recharging steps do not mention draining. |
| Baxi 600 Combi 2 | With the system cold, relieve the pressure by draining the boiler and check at the valve under the vessel. Adjust and repressurise. Check the pre-charge every year and restore it to 1 bar if necessary. |
| Glow-worm Energy7 | Section 12.13 drains the product, and 12.14 then measures at the vessel valve. Below 0.75 bar, top up to suit the static height, ideally with nitrogen, otherwise air, with the drain valve open. Water from the valve means the vessel is replaced. |
How do you work out the right pre-charge?
From the static head. Worcester Bosch counts 0.1 bar per metre, measured from the vessel to the top of the highest radiator, and Glow-worm says the charge must not be less than that static head. Two worked examples using the manuals' own rules and tables.
| Example | Working | Result |
|---|---|---|
| Greenstar 4000, highest radiator 9 m above the vessel | 9 m x 0.1 bar = 0.9 bar static head, above the 0.75 bar default. Choosing the manual's 1.0 bar curve, the system is set 0.1 to 0.25 bar higher. | Vessel at 1.0 bar, system filled to 1.1 to 1.25 bar, and the curve read for system volume and flow temperature to see if an extra vessel is needed. |
| Logic Combi2 on a 125 litre system | Table 4 needs 7.8 litres of vessel with no system pre-pressurisation, or 9.2 litres if the system is pre-pressurised to 1.0 bar. | The 8 litre vessel covers the first case. In the second an extra vessel goes on the return to the boiler, as section 1.16 says. |
What does it mean if the pressure keeps rising?
Worcester Bosch's system gassing flow chart (fig. 103) starts there. If the pressure climbs above 2.5 bar when the boiler is on, it asks whether the vessel is charged higher than expected; if it is not, whether the charge is too low, and if so, re-pressurise the vessel. If the charge is correct, check the vessel is sized for the system. A pressure that keeps falling with a dripping relief valve points it at the valve instead.
Only a Gas Safe registered engineer can size, install, service or certify a boiler, and the vessel sits inside the case. This page reports what five manuals print for one range each; the manual for the exact model fitted governs, and a cylinder's own vessel follows the cylinder maker's manual.
An unvented cylinder carries its own expansion vessel or air volume, set by the cylinder maker, and the G3 guide covers that. Manifold produces the gas service record from the check you complete on your phone at the property.
Read next
Frequently asked
Sources
- Worcester Bosch, Greenstar 4000 combi installation manual (6720891161, 2021/10), pages 13, 43, 82 and 84
- Vaillant, ecoTEC plus installation and maintenance instructions (0020244997_07), technical data and sections 9.13 and 12.15
- Ideal Heating, Logic Combi2 C24, C30, C35 installation and servicing manual (UIN 237664 A08), sections 1.16, 3.2 and 3.31
- Baxi, 600 Combi 2 installation and servicing manual (7745721), sections 5.2.8 and 10.3.3
- Glow-worm, Energy7 combi installation and maintenance instructions (0020300875_01), sections 9.7, 12.13 and 12.14